Humidistat, thermostat with two relay outputs. Outdoor, indoor use.
Relative humidity, temperature probe on a cable. Measured values are also converted to other humidity interpretation: dew point temperature, absolute humidity, specific humidity, mixing ratio, specific enthalpy. Three two-state inputs.
The device is supplied with T+RH probe with 1 meter cable.
Technical data
Measured value
Temperature
Relative humidity
Counted values (dew point…)
Two-state signal
TEMPERATURE SENSOR
Measuring range
-30 to +105 °C
-30 to +105 °C
Accuracy
±0.4 °C
±0.4 °C
Resolution
0.1 °C
0.1 °C
HUMIDITY SENSOR
Measuring range
0 to 100 % RH
0 to 100 % RH
Accuracy
±2.5 % RH from 5 to 95 % at 23 °C
±2.5 % RH from 5 to 95 % at 23 °C
Resolution
0.1% RH
0.1% RH
DEW POINT
Measuring range
-60 to +80 °C
-60 to +80 °C
Accuracy
±1.5 °C at ambient temperature T <25 °C and RH >30 %
±1.5 °C at ambient temperature T <25 °C and RH >30 %
Resolution
0.1 °C
0.1 °C
RELAY OUTPUTS
Quantity
2
2
Maximal voltage
50 V
50 V
Maximal current
2 A
2 A
Maximal power
60 VA
60 VA
BINARY INPUTS
Quantity
3
3
Signal for binary inputy
dry contact, open collector or two-state voltage signal.
Inputs are not galvanically isolated.
dry contact, open collector or two-state voltage signal.
Inputs are not galvanically isolated.
Minimum pulse duration on binary input
500 ms
500 ms
Voltage across open contact
< 3,3 V
< 3,3 V
Low voltage level
0 to +0,5 V
0 to +0,5 V
High voltage level
+3,0 to +30 V
+3,0 to +30 V
GENERAL TECHNICAL DATA
Operating temperature
-30 to +80 °C
-30 to +80 °C
Channels
1x connectable temperature+humidity probe
1x connectable temperature+humidity probe
Counted values
dew point, absolute humidity, specific humidity, mixing ratio, specific enthalpy
dew point, absolute humidity, specific humidity, mixing ratio, specific enthalpy
Acoustic alarm
from built-in beeper – switchable
from built-in beeper – switchable
Output
RS485
RS485
Range of humidity sensor temperature compensation
all temperature range
all temperature range
Available temperature units
degrees Celsius, degrees Fahrenheit
degrees Celsius, degrees Fahrenheit
Communication protocol
ModBus RTU, ARION, Advantech ADAM
ModBus RTU, ARION, Advantech ADAM
Power
9-30 Vdc
9-30 Vdc
Protection class
IP65 electronics; IP40 sensors
IP65 electronics; IP40 sensors
Dimensions
136 x 159 x 45 mm; length/diameter of external probe 88/18 mm
136 x 159 x 45 mm; length/diameter of external probe 88/18 mm
External probe cable length
1 meter
1 meter
Weight
approx. 500 g
approx. 500 g
Warranty
3 years
3 years
code